Universal anchors
Single-bracket anchors EK-U
Your advantages at a glance:
- Constant stock of standard sizes for fast delivery
- Flexible use, with or without intermediate bracket
- Height-adjustable
- Wall clearances greater than 200 mm are also possible for increased thermal insulation. As well as our MOSO support brackets, we will also obtain specific approval for our air gap wire anchor based on DIN 1053
- Matching, approved air gap wire anchors included in delivery
Use and application
- • Particularly suitable for invisibly supporting large wall surfaces.• Variable anchor spacing (ak) depending on load and brick format (25 cm intervals).• Install anchors at intervals ak and loosely fit intermediate brackets type WA-Z in between if necessary.• The brackets must be fully supported until the brick mortar has set hard.Particularly suitable for invisibly supporting large wall surfaces.
- Variable anchor spacing (ak) depending on load and brick format (25 cm intervals).
- Install anchors at intervals ak and loosely fit intermediate brackets type WA-Z in between if necessary.
- The brackets must be fully supported until the brick mortar has set hard.

View tables
|
Type / Version Type /Version
| Load stage | 3,5 kN | 7,0 kN | 10,5 kN | ||||
|---|---|---|---|---|---|---|---|---|
| Distance/wall | Cantilever length K | Bracket height x | Cantilever length K | Bracket height x | Cantilever length K | Bracket height x | ||
|
| 20 - 50 | 130 | 150 | 130 | 200 | 130 | 250 | |
| 40 - 70 | 150 | 150 | 150 | 200 | 150 | 250 | ||
| 60 - 90 | 170 | 150 | 170 | 200 | 170 | 250 | ||
| 80 - 110 | 190 | 150 | 190 | 200 | 190 | 250 | ||
| 100 - 130 | 210 | 150 | 210 | 200 | 210 | 250 | ||
| 120 - 150 | 230 | 175 | 230 | 250 | 230 | 300 | ||
| 140 - 170 | 250 | 175 | 250 | 250 | 250 | 300 | ||
| 160-190 | 270 | 175 | 270 | 250 | 270 | 300 | ||
| 180-200 | 290 | 175 | 290 | 250 | 290 | 300 | ||
| Wall clearances greater than 200 mm available on request | ||||||||
| Supporting plate | B / L / S | 80 / 60 / 3 | 80 / 60 / 4 | 80 / 60 / 5 | ||||
| Max. size of fastener | up to M12 | up to M12 | up to M16 | |||||
| Shear connector for uncracked concrete > C20/25 (compression zone) | UPAT UKA3 M10x165 Distance from edge ar ≥ 110
| UPAT UKA3 M12x190 Distance from edge ar ≥ 135 | UPAT UKA3 M16x215 Distance from edge ar ≥ 155 | |||||
| Shear connector for cracked concrete > C20/25 (tension/compression zone) | Fischer FHB II-AS M10x60/60 Distance from edge ar ≥ 100 | Fischer FHB II-AS M12x75/60 Distance from edge ar ≥ 140 | Fischer FHB II-AS M16x95/60 Distance from edge ar ≥ 140 | |||||
| HK screw on supporting anchor rail in concrete > C20/25 | MHK 38/17 M12x80 Distance from edge ar ≥ 75 | MHK 50/30 M12x80 Distance from edge ar ≥ 150 | MHK 50/30 M16x100 Distance from edge ar ≥ 200 | |||||
| Bear anchor rail | MBA 38/17K | MBA 50/31 | MBA 52/34 | |||||
| Values apply for facing bricks 115 mm thick with a superimposed load < 2 soreys, otherwise the anchors must be adapted in accordance with DIN 1053. Other dimensions on request | ||||||||
| Superimposed Load(m) | Load (kN/m) | Anchor spacing ak (m) | Load stage | Intermediate |
|---|---|---|---|---|
| < 1,5 | < 3,105 | 1 | 3,5 | WA-Z-95/50/3-980 |
| < 2 | < 4,14 | 0,75 | 3,5 | WA-Z-95/30/3-730 |
| < 3 | < 6,21 | 0,5 | 3,5 | WA-Z-95/20/2-480 |
| < 4,5 | < 9,315 | 0,75 | 7 | WA-Z-95/30/3-730 |
| < 6 | < 12,42 | 0,5 | 7 | WA-Z-95/20/2-480 |
| < 9 | < 18,63 | 0,5 | 10,5 | WA-Z-95/20/2-480 |
| < 12 | < 24,84 | 0,375 | 10,5 | WA-Z-95/20/2-360 |
| (Assuming a 115 mm wide facing brick with γ=18kN/m³. Note individual evidence of attachment!) | ||||
| Subject |
|---|
| Individual evidence of attachment in the anchorage base:
|
|
Installation instructions for MOSO supporting anchors:
|